image006
 
image010

RVS-DN line of Low Voltage Soft-Starters

RVS-DN

Which soft starter is considered as the most reliable soft starter in todays' Industrial and Marine markets ?

The RVS-DN is a severe duty, Full Featured, Motor Protection enhanced, Microprocessor-Based, for Motors 4-3500A, 4-3000KW, 208-690V.

For 1000V and 1200V click << RVS-DN for 1000V and 1200V

For 2300V to 15000V click << HRVS-DN Medium Voltage Soft Starter >>.0

View these soft starters in demanding environmental conditions check out our Naval, Marine, Industial, Oil and Gas examples of Solcon soft-starters in a variety of applications

Advantages at a Glance

  • Eliminates high inrush current and damaging mechanical shock
  • Third generation microprocessor circuitry
  • Heavy duty design: 50°C ambient temperature
  • Soft, stepless acceleration & deceleration
  • Power factor capacitors can be connected directly to the upstream contactor
  • Unique starting & stopping characteristics (special characteristics for Ex motors)
  • Unique features such as: Pump Control Program, Dual Adjustment, Slow Speed with Electronic Reversing, Energy Save, etc.
  • Torque and current starting & stopping characteristics
  • Sophisticated motor protection package with Enhanced features
  • User friendly, easy installation and operation
  • RS485 Communication with MODBUS, PROFIBUS or MODBUS/TCP protocols (others available on request)
  • Wide 45-65Hz Auto-tracking frequency range combining special software with unique hardware arrangement allowing starting and stopping while the frequency variates (designed for Marine, Offshore and Generators operating under continuous frequency variation
  • Possibility to operate without bypass contactor at 50°C up to 820A

 

RVS-DN Protection Features

  • Start & start inhibit with time delays
  • Long start time (Stall protection)
  • Electronic shear-pin (Jam) with adjustable curves and delay
  • Electronic overload with selectable curves
  • Under current with programmable auto reset
  • Phase loss
  • Phase sequence and Under/Over frequency
  • Under/Over voltage with programmable auto reset
  • Load loss (indentifying broken drive belt, lack of water in a well, etc.)
  • External fault
  • Shorted SCR
  • Starter over temperature protection
  • Motor insulation test (option)
  • Motor thermistor (option)
  • Analogue Ouput (option)
  • When using "Preparation for Bypass" all protective functions remain active

 

RVS-DN Control

  • All inputs & outputs are isolated
  • Three C/O output relays
  • Thermistor input
  • Analogue output
  • Communication RS 485 with MODBUS RTU or MODBUS Plus protocols
  • User friendly keypad interface allowing precise settings
  • Bright LEDs for immediate visual interface
  • Interactive and informative 4 language LCD for easy trouble shooting
  • Statistical data
  • Motor insulation protection
  • Hardware and software integration to allow starting from diesel-generator


RVS-DN Construction

  • Heavy duty fully rated design (ambient 50°C)
  • Compact, light weight
  • Cost efficient plug-in control module, identical for sizes B-G
  • Preparation for bypass contactor (option), maintaining protection after the bypass contactor is closed


RVS-DN with Motor Protection Features Typical Applications

  • Pumps (Water utilities, Industry)
  • Compressors
  • Conveyors & monorails
  • Mixers & Agitators
  • Fans & Centrifuges
  • Hydraulic pumps
  • Starting from weak Mains supply
  • Marine (Thrusters, pumps, fans, refrigeration, compressors, etc..)


RVS-DN-AG for two phase motors with Motor Protection Features Typical Applications

Special applications - please contact us

rvs-dn-2

RVS-DN Soft Starter

Starter Type Motor KW Motor HP Starter Size Dimensions (mm) & Weight
V~ +10% : -15% V~ +10% : -15%
230V 380-440V 500V 690V 230V 460V 575V A-G W H D Kg
RVS-DN 8 2.2 4 5.5 7.5 3 5 7.5 A 153 310 170 5
RVS-DN 17 4 7.5 11 15 5 10 15 153 310 170 5
RVS-DN 31 7.5 15 16.5 22 10 20 30 153 310 217 7
RVS-DN 44 11 22 30 37 15 30 40 153 310 217 8
RVS-DN 58 15 30 37 45 20 40 50 153 310 217 8
RVS-DN 72 18.5 37 45 55 25 50 60 153 310 217 8
RVS-DN 85 22 45 55 65 30 60 75 B 274 370 279 15
RVS-DN 105 30 55 75 90 40 75 100 274 370 279 15
RVS-DN 145 37 75 90 132 50 100 125 274 370 279 15
RVS-DN 170 45 90 110 160 60 125 150 274 370 279 15
RVS-DN 210 55 110 132 185 75 150 200 C 590 500 275 45
RVS-DN 310 90 160 220 250 100 200 300 590 500 275 45
RVS-DN 390 110 200 250 315 125 250 350 590 500 275 45
RVS-DN 460 132 250 315 450 150 300 400
623 660 290 65
RVS-DN 580 160 315 400 500 200 400 500
623 660 290 65
RVS-DN 820 250 450 600 750 300 600 700 623 660 290 65
RVS-DN 950 295 500 670 925 400 815 1030 D 623 660 290 83.5
RVS-DN 1100 355 630 800 1000 400 800 1000 723 1100 370 170
RVS-DN 1400 400 800 900 1300 500 1000 1250 723 1100 370 170
RVS-DN 1800 560 950 1250 1500 600 1250 1500 E 723 1100 370 170
RVS-DN 2150 NA 1250 1500 2000 700 1500 2000 F 750 1300 392 235
RVS-DN 2400 NA 1400 1750 2250 800 1750 2250 900 1300 360 350
RVS-DN 2700 NA 1550 2000 2500 900 2000 2500 G 900 1300 360 350

 

rvs-dn-4

* Type test (DNV is type approved as of April 2006)

Notes:

  • RVS-DN 8 through RVS-DN 820 are UL & cUL and SCCR Approved (does not apply to RVS-DN-AG, SCCR applies to slim version )
  • RVS-DN 1100 and above are designed to meet UL & cUL requirements
  • Contact us for RVS-DN 210, 310, 390, 460, 580, 820 & 950 Slim version (Narrow)
  • Select the starter according to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the motor is not fully loaded)
  • The selection table above, concerns standard, 1500 R.P.M. 50Hz, three-phase asynchronous motors. These values are given for guidance and may vary according to individual motor manufacturers (as well as number of poles)
  • It is the user's responsibility to verify that motor's FLA does not exceed Starter's FLC