MPR-6/3-DGF Motor Protective Relay
With Directional Ground Fault Function & 3 Thermal Sensors
General

The MPR-6/3 incorporates two main functions.
a. Motor protection.
b. Supervision and communication.
A comprehensive protection device is required to accurately create a Thermal Model for the motor to run safely up to its limits.
This relay should protect the motor from abnormal conditions in the power supply, motor and cable faults as well as operator malfunctions.
The MPR-6/3 monitors three phase currents (true RMS line currents are measured at a sampling rate of 0.5 mSec). The MPR-6/3 monitors ground fault current (true RMS) and zero sequence voltage (3Vo), for Directional Ground Fault protection. The MPR-6/3 monitors three temperature (RTD or PTC/NTC Thermistor) inputs. Finally, the MPR-6/3 provides a comprehensive protection package.
Protection
- Too many starts
- Maximum start time
- Under current
- Load increase
- Thermal level (Overload) - Two Levels
- Over-current Jam / Stall & Short circuit – Two Levels
- Unbalanced current – Two Levels
- Directional Ground fault current
- Phase Sequence
- Temperature (3 Sensors)- RTD Pt.100 or 3 PTC/NTC Thermistor - Two Levels
- External fault 1- N.O/N.C contacts
- External fault 2 - N.O/N.C contacts
Inputs
- 3 , 5A Phase C/T's (1A is also available)
- 2 , Programmable Discrete inputs
- 1 , Residual Ground Current Input
- 1 , Open Delta Voltage Input
- Control Voltage Supply (115,230VAC 50/60Hz,110VDC)
- 3 , RTD/Thermistors
Outputs
- 1 , Alarm Relay fail safe (8A/250V)
- 1 , Trip Relay trip/trip-fail safe (8A/250V)
- 2 , Programmable (8A/250V)
- 1 , Programmable Analog Output
HMI
- 2 Lines Illuminated LCD
- 4 , LED's
Communication
- RS485 Serial Limk With Modbus / Profibus Protocol at baud rate of 1200 to 9600 bit/sec
Actual Data
- I1 , I2 , I3 Phase Currents
- T1 , T2 , T3 RTD's Temperatures
- % of Motor FLC
- Unbalance Current
- I0 Residual Current , 3V0 Zero Sequence Voltage
- Thermal Capacity
- Time to Trip
- Time to Start
Statistical Data
- Last Start Period
- Last Start Max. Current
- Last Trip Thermal Level 2
- Last Alarm Thermal Level 1
- Trip I1 , I2 , I3
- Trip I0 , 3V0
- Trip T1 , T2 , T3
- Total Run Time
- Total Number of Starts
- Total Number of Trips
Codes & Standards
Impulse :IEC 255-4 (1976) & Amend #1 (1979)IEC 255-5 (1977)
5 kV common-mode test
5 kV transverse-mode test
Surge withstand :
Oscillatory 2.5 kV peak
Fast transient 4 kV crest voltage
In accordance with: ANSI C37.90.1 (1990), IEC 55-4 (1976)
Amend #1 (1979) Class III, IEC 255-22-2 (1988) Class III
RFI : In accordance with EMI standard ANSI C37.90.2
Technical Specification
Auxiliary Power Supply110VDC.
Consult factory for 230VAC (165 - 260V), 115VAC (88 - 125V), (to be specify). 45 to 65Hz.
Power consumption: ≤ 10VA
Current Measurement (three currents) Method : True rms.
Range: 0.05 to 12 * phase CT Primary amps setting. Note: I1 is used to measure mains frequency. Lower (< 0.05) current may cause wrong
frequency measurement which may cause inaccurate currents and voltage measurements.
Full scale: 12 * phase CT Primary amps setting.
Accuracy : ± 1.5% , for 0.9 to 1.5 * CT Primary amps setting.
± 5% above 1.5 * CT Primary
± (3% + 0.02 * CT Primary) below 0.9 * CT Primary
Power consumption: ≤ 0.1VA per 1A at 1Amp. input, (Input impedance ≤ 100mΩ)
≤ 0.5VA per 5A at 5Amp. input, (Input impedance ≤ 20mΩ)
Directional Ground Fault 3Vo measurement Method : True RMS.
Rated input Voltage 110V / 190V.
Measurement Range: 5V to 30V. Measured with 200mA / 1.5mA ZCT.
Full scale: 30V.
Accuracy : ± 3% of full scale.
Input impedance: ≥ 50KΩ
Allowed input range: <= 220VAC (saturated, no damage)
Phase accuracy: ± 10°
Directional Ground Fault Current measurement (ZCT primary current) Method : True RMS.
Measurement Range: 0.1 to 1.0A at ZCT Primary, when measured with 200mA / 1.5mA ZCT.
0.75mA to 7.5mA at ZCT secondary.
Full scale: 1A (saturated, no damage).
Accuracy : ± 3% of full scale.
Input impedance: ≤ 10Ω
Allowed input range: <= 1A at ZCT secondary (at relay input terminals).
Phase accuracy: ± 10°
| Thermistor Input | RTD Input | |
| Range: 0.1 - 30KΩ. | Range: 100 - 240Ω or 0°C - 250°C | |
| Accuracy: ± 0.1KΩ up to 5KΩ, ± 3% above 5KΩ | . | Accuracy: ± 3% of resistance. |
| Time delay: 2 Sec | Max wire resistance: 25Ω. |
Overload Alarm and Trip Curves (both heating and cooling)
Fault time accuracy: ± 1 Second up to 10 seconds.
± 1 second ± 2% above 10 seconds.
Threshold current level : OVERLOAD PICKUP ± 1.5%.
Total Run Time
Accuracy: ±2%.
Current Unbalance Alarm and Trip
Method: Unbalance = 100 * (Imax - Imin) / Ir [%]
Where: Imax = max. of the three phase currents.
Imin = min. of the three phase currents.
Ir = larger of (Imax , Motor FLC setting).
(to prevent nuisance tripping at low current levels) Alarm
Threshold unbalance alarm level: 50% of Unbalance Current setting ± 2%.
Alarm (fixed) time delay: 5.0 ± 0.5 Sec.
Trip Curves
Threshold unbalance trip Level: Unbalance Current setting ± 2%.
Trip time accuracy: ± 1 Second up to 10 seconds. ± 1 second ± 2% above 10 seconds.
Oredering Information


Dimensions







